What is the default login for WebBrix?
The default username is "Admin" and the password is blank.
|
Where is the error log located?
The default location of the error log is C:\Documents and Settings\All Users\Application Data\WebBrix\AMTErrorlog.txt
You can change this location by modifying the following registry entry: HKEY_LOCAL_MACHINE\SOFTWARE\AMT\Install\AMTErrorLogPath
|
Why can't I open the Cardset Configuration utility ?
This is a known issue with WebBrix 2.8.0. In order to run this utility, you must be log into the computer as the same user that was assigned to run the services.
|
I don't see any controllers in the list of available hardware to discover...
This could be caused by numerous things. Here are some things to check.
| • | Is the controllers Host IP property set to the IP address of the target Hardware Server? |
| • | Is the controllers HereIAm property set to something greater than 0? (we recommend 30 seconds) |
| • | Is a firewall blocking communication between the hardware and the PC? (ports 4050 and 4070) |
|
What are "Conditions" and how do I use them?
"Conditions" are placeholders for a future feature of WebBrix.
|
How do I change a controllers time zone after discovery?
To change the time zone of a controller after the initial discovery, direct database access is required. In the controllers table of the Gateway database, there is a field named GMTOffset.
|
Does WebBrix require IIS to be installed?
IIS is highly recommended, but not required. If the install is started and IIS isn't installed, the install will offer to install Cassini. Cassini is a lightweight web server and is limited to local hosting only.
|
Which operating systems does WebBrix support?
Windows XP Professional (latest service pack) and Windows 2003 Server (latest service pack)
|
What happens when the grace period expires?
The system will continue to function but the software will continually open a "nag" window, reminding the user to license the software.
|
When I have a valid card read why does my door unlock and lock instantaneously?
It's likely the door monitor switch is wired backwards. To fix tihs, reverse the wires or change the door monitor behavior for that reader in the software.
|
When I start the software I receive a message box telling me the software is running in grace period. What does this mean?
When you have exceeded the capacity for a given feature, the grace period notification will appear. For new installs, there is a 14 day grace period.
|
What does the term "grace period" refer to?
The amount of time the system can run after it has exceeded its licensed capacity.
|
Do you require IIS to be enabled?
Yes, WebBrix does require IIS to be enabled
|
When I have a valid card read why does my door unlock and lock instantaneously?
The door monitor switch is wired backwards. Reverse the wires or change the position setting in the WebBrix.software.
|
The controller time is not correct?
There's a GMT offset field in the controllers table that takes care of this(CST would be -6 hours from the GMT and the field is in minutes, so the value would be -360) The WebBrix updates the controllers time once every hour on the 1/2 hour(1:30, 2:30, 3:30, etc...)
|
Where are the install logs located?
Navigate to C:\Program Files\WebBrix\InstallLogs
|
How can I tell if the services running?
Navigate to Control panel/administrative tools/services and check the status.
|
What services need to be running for proper operation?
AMTLicenseMgr, AMTNetworkComm and DCS
|
What versions of VertX firmware are currently supported?
2.2.7.33, 2.2.7.38, 2.2.7.39.
|
The panel is not communicating withWebBrix. What should I check first?
Power to the panel. The correct network settings: Panel IP, subnet, qateway host IP, firewall settings.
|
What should the Here I am Interval (sec) on the panel be set to?
30 seconds is recommended.
|
What's the power specification for the VertX panels?
What's the max current specified for the VertX panels at 12 VDC?
How does the VertX panel communicate with a host system?
Ethernet on a TCP/IP network using ports 4050 and 4070 (by default).
|
What forms of communication does the V1000 support downstream?
RS-232 serial port and a multi-drop RS-485
|
How far can the input and output circuits extend?
500 feet using 2 conductor shielded 22AWG cable.
|
How far can the Wiegand signal travel between the reader and the panel?
500 feet using 22AWG 9 conductor stranded with an overall shield.
|
How far can Ethernet extend?
328 feet using Cat5, Cat5E and Cat6
|
How many panels can 1 V1000 controller support?
16 panels (V100, V200, V300) can reside on 1 port of the V1000. The V1000 has 4 ports for a total of 64 panels
|
SWhat topology is used when connecting the RS-485 busses?
What does the Terminal EOL Resistor jumper do on a V1000?
This resistor setting aids in the overall communication efficiency of the ports for the V1000. In order to increase communication efficiency the resistor jumper should be set to "In" if there are no devices using that port.
|
Where do I locate the system Uniqueness?
Navigate to start/programs/WebBrix/License Editor
|
How do I restore from a backup?
Navigate to start/programs/WebBrix/Database Maintenance and click on the "Restore" tab. Select the date from the list and click "Restore"
|
What is the numbered dial for on the front of the V100, V200 and V300?
The dial is used for unique addressing for each individual panel on a multi-drop RS-485 port.
|
What does the Terminal Resistor jumper do on a V100, V200, V300?
The Terminal Resistor jumper is set to the “Out” position on all panels with the exception of the last one on the RS 485 multi-drop. The last panel on this drop should be set to the “In”.
|
What kind of battery is recommended for the V1000/V2000?
3V coin type Lithium battery. Part# CR2032
|
What happens if the battery is not installed?
What is the operating temperature of the VertX panels?
How far can a RS-485 run extend?
4000 feet using 22AWG twisted pair shielded 100Ω cable.
|
Can I set the backup to automatically archive?
No. It is a manual process. Once a backup has been created you can store it in a location that is automatically backed up on the network.
|
Where do I send requests for regcodes?
Where do I send requests for support?
|